Final | 4/19/2007 | 4/19/2007 | 4/19/2007 | P | PASS |
Bob Reichert
|
|
|
Glen; Phone #: ###-#### Internet Inspection Request from: Stacie Backus corr made, ok to final
|
Final | 4/18/2007 | 4/18/2007 | 4/18/2007 | P | FAIL |
Bob Reichert
|
|
|
glenn ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left corr notice, nec 110.22 each disconnect shall be legibly marked to indicate it's purpose,406.5 faceplates shall seat against mounting surface, 410.8(A) edge of fixture in closet shall be min 12" from edge of shelf
|
Permanent Service | 3/9/2007 | 3/9/2007 | 3/9/2007 | P | PASS |
Bob Reichert
|
|
|
glen; Phone #: ###-#### Internet Inspection Request from: Stacie Backus p/s u/g n ok
|
Rough-In Permanent Service | 3/6/2007 | 3/6/2007 | 3/6/2007 | P | PART |
Jack Frank
|
|
|
glenn; Phone #: ###-#### Internet Inspection Request from: Patricia Smith concrete encased electrode ok
|
Rough-In Permanent Service | 2/28/2007 | 2/28/2007 | 2/28/2007 | P | CANC |
Bob Reichert
|
|
|
glen; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, gec not poured, therefore ric only, see ri, will do gec ltr
|
Electrical Rough-In | 2/27/2007 | 2/28/2007 | 2/28/2007 | A | CANC |
Bob Reichert
|
|
|
Glen grounding and rough in; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called contr, wrong address
|
Application received | | | 2/27/2007 | | |
|
|
|
|
Override - Parcel Holds | | | 2/27/2007 | | |
|
|
|
NOthing to do with parcel hold
|
Issue permit | | | 2/27/2007 | | DONE |
|
|
|
|