Final | 7/30/2012 | 7/31/2012 | 7/31/2012 | A | PASS |
Bob Reichert
|
|
|
Justin Phone #: ###-#### ok final, corrections made
|
Final | 7/19/2012 | 7/19/2012 | 7/19/2012 | P | FAIL |
Bob Reichert
|
|
|
Justin-Please call for access information Phone #: ###-#### shall replace gfci in kitchen, shall provide outlets in islands, shall provide manufacturers instructions for jetted tub access
|
Change Status to I | | | 7/19/2012 | | DONE |
Barbara Stitt
|
|
|
Re=open expired permit for final inspection per Bob Archibald//BAS
|
Telephone call | | | 4/5/2012 | | DONE |
Tisha Gallop
|
|
|
Jayo Construction called, said he still had original plans and project is done. Told him need to pay 2 hr admin fee on this building permit and need to have E-Zee Elec reopen electrical permit Ele for 2 hr admin fee and need to have Wedge Plumbing reopen plumbing permit Plm for 2 hr admin fee. Terry Records also needs to sign off on building permit before we can issue the residential c of o because he only signed off for part.
|
ELE-Aging Inspection | 2/10/2010 | 2/10/2010 | 2/18/2010 | | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 2/18/2010 | 2/18/2010 | 2/18/2010 | A | PASS |
Jack Frank
|
|
|
no activity
|
ELE-Aging Inspection | 12/10/2009 | 12/10/2009 | 12/16/2009 | | DONE |
Bob Reichert
|
|
|
no activity, suc
|
ELE-Aging Inspection | 10/7/2009 | 10/7/2009 | 10/7/2009 | P | DONE |
Bob Reichert
|
|
|
no activity, suc, waiting for contractor call for inspection
|
ELE-Aging Inspection | 9/2/2009 | 9/2/2009 | 9/2/2009 | A | DONE |
Bob Reichert
|
|
|
no activity, suc, no inal requested yet
|
Electrical Rough-In | 3/3/2008 | 3/4/2008 | 3/4/2008 | A | PART |
Jack Frank
|
|
|
Need O.K. to cover ditch for post lights. Ditch at East side of house. Joe Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt ok
|
Electrical Rough-In | 1/8/2008 | 1/9/2008 | 1/9/2008 | A | PART |
Mike Kinnear
|
|
|
Wire for post lights in planter boxes in front of house. Need O.K. to cover conduit. Joe Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt ok cover in the walls & planters only no under ground
|
Electrical Rough-In | 11/9/2007 | 11/9/2007 | 11/9/2007 | P | PASS |
Bob Reichert
|
|
|
joe Phone #: ###-#### ok to cover floor heat main bath only
|
Rough-In Permanent Service | 3/27/2007 | 3/28/2007 | 3/28/2007 | A | PASS |
Bob Reichert
|
|
|
Joe Phone #: ###-#### called contr, no plans on job, talked about jetted tubs, access, need to check at final, corrections made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 3/17/2007 | 3/19/2007 | 3/19/2007 | A | FAIL |
Jack Frank
|
|
|
Joe Phone #: ###-#### corr. called BCC needs plans at site , all boxes , light fixtures shall be installed, all framing complete so elect. contr can wire walls, 250.66 install correct size bond to water pipes 210.52(A) outlets for wall space, 210.52(B) remove fam. rm from kit circuit, protect cables by attic accesses
|
Electrical Rough-In | 3/14/2007 | 3/14/2007 | 3/14/2007 | A | PASS |
Bob Reichert
|
|
|
Bob, just the outside sofits, front and back we need O.K. to cover. Thanks. Joe Phone #: ###-#### ok to cover soffits, called to ensure stapling nm cable
|
Electrical Rough-In | 3/6/2007 | 3/6/2007 | 3/6/2007 | P | PART |
Bob Reichert
|
|
|
joe ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to cover lower rear soffit only
|
Application received | | | 3/2/2007 | | |
|
|
|
|
Issue permit | | | 3/2/2007 | | DONE |
|
|
|
|