Final | 5/29/2007 | 5/29/2007 | 5/29/2007 | P | PASS |
Bob Reichert
|
|
|
Craig ###-#### corrections made, ok to final
|
Final | 5/25/2007 | 5/25/2007 | 5/25/2007 | P | FAIL |
Bob Reichert
|
|
|
craig; Phone #: ###-#### - please call for access Internet Inspection Request from: Victoria Beall called, left corr notice, nec 422.16(B)(2) disposal cord shall not be over 3', 408.4 circuit directory shall be clear, concise and direct for each ckt, 210.12(B) bedrooms shall have afci protection, 422.31(B) shall provide lockout or disconnect for hw heater, 410.8(D) shall have minimum 12" from edge of shelf to edge of fixture in closet, 406.4(D) faceplates shall allow recpts to be flush with or project from faceplate, 410(D) luminaire within 3' of shower shall be listed for wet location if subject to shower spray, BCC kitchen gfci shall operate, 3-way switch to basement shall be wired correctly, nec 110.26 shall provide clearances at garage panel, 250 shall provide grounding for garage
|
Electrical Rough-In | 3/8/2007 | 3/8/2007 | 3/8/2007 | P | PASS |
Bob Reichert
|
|
|
seth; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt corr made, ric ok, see p/s
|
Permanent Service | 3/8/2007 | 3/8/2007 | 3/8/2007 | P | PASS |
Bob Reichert
|
|
|
seth; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt corr made, p/s o/h rec ok
|
Electrical Rough-In | 3/5/2007 | 3/6/2007 | 3/6/2007 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/5/2007 at 4:55:32 PM. Contact: ###-####. called, left message, nec 250.92 (A)(3) metallic raceway enclosing gec shall be bonded at each end, 250.53(C)(2) water system shall be supplemented by electrodes and bonded to grounded service conductor, 250.70 listed and approved connections shall be used for gec, 352.30(A) rnc shall be securely fastened within 3' of termination, 314.17(C) nm cable shall be secured within 8"of box, 210.52(A)(2) wall spaces over 2' shall have recpt installed, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 210.52(E) shall provide outlet at front of dwelling, 110.26(F)(1)(a) there shall be no foreign piping systems over equipment, 110.12(A) there shall be no broken parts (boxes), 300.14 at least 6" of free conductor shall be in each box, Bcc all make-up shall be done, grounds together, Reserved right to amend corr notice, left do not cover sticker
|
Application received | | | 3/5/2007 | | |
|
|
|
|
Issue permit | | | 3/5/2007 | | DONE |
|
|
|
|