Final | 4/19/2007 | 4/19/2007 | 4/19/2007 | P | PASS |
Bob Reichert
|
|
|
Glen; Phone #: ###-#### Internet Inspection Request from: Stacie Backus corr made, ok to final
|
Final | 4/18/2007 | 4/18/2007 | 4/18/2007 | P | FAIL |
Bob Reichert
|
|
|
glenn ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left corr notice, nec 352.30(A) rnc shall be strapped within 3' of termination,110.22 each disconnect shall be legibly marked to show it's purpose, 410.8(A) edge of fixture shall be min 12" from edge of shelf
|
Rough-In Permanent Service | 3/9/2007 | 3/9/2007 | 3/9/2007 | P | PASS |
Bob Reichert
|
|
|
glen; Phone #: ###-#### Internet Inspection Request from: Stacie Backus u/g to garage ok, ok to backfill gec, ric ok, p/s u/g n ok
|
Permanent Service | 3/6/2007 | 3/6/2007 | 3/6/2007 | P | CANC |
Jack Frank
|
|
|
glenn - ground reinspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see added r/i
|
Electrical Rough-In | 3/6/2007 | 3/6/2007 | 3/6/2007 | P | PART |
Jack Frank
|
|
|
glenn - ground reinspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith electrode ok for concrete cover only
|
Application received | | | 3/6/2007 | | |
|
|
|
|
Override - Parcel Holds | | | 3/6/2007 | | |
|
|
|
|
Issue permit | | | 3/6/2007 | | DONE |
|
|
|
|