Final | 9/21/2007 | 9/24/2007 | 9/24/2007 | A | PASS |
Bob Reichert
|
|
|
ken Phone #: ###-#### corrections made, ok to final
|
Final | 9/19/2007 | 9/19/2007 | 9/19/2007 | P | FAIL |
Bob Reichert
|
|
|
ken Phone #: ###-#### met owner, left corr notice, nec 410.8(D) fluorescent fixture shall be minimum 6" from storage space, 210.12(B) all bedroom outlets shall be protected by afci, 422.31(B) shall provide breaker lock-out for water heater
|
Electrical Rough-In | 5/8/2007 | 5/9/2007 | 5/9/2007 | P | PASS |
Bob Reichert
|
|
|
KENNETH ; Phone #: ###-#### Internet Inspection Request from: Darla Downs corr made, ric ok
|
Electrical Rough-In | 5/4/2007 | 5/7/2007 | 5/7/2007 | A | NR |
Pat Lass
|
|
|
ken ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith R/I Ok had conf. about box fill free conductor protection of conductors lolcation of closet light and panel and electrodes bonding together amd requirements for r/i inspection.
|
Application received | | | 3/13/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 3/13/2007 | | DONE |
|
|
|
|