Final | 7/2/2007 | 7/3/2007 | 7/3/2007 | A | PASS |
William E Thomas
|
|
|
Key located in center of window on left side of front door Phone #: ###-#### Internet Inspection Request from: Therrin Robertson 1. final ok 2. survey note--210.52 counter recep by corner sink
|
Electrical Rough-In | 3/20/2007 | 3/20/2007 | 3/20/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### corr made, ric ok
|
Rough-In Permanent Service | 3/16/2007 | 3/19/2007 | 3/19/2007 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### see ri, and p/s
|
Electrical Rough-In | 3/19/2007 | 3/19/2007 | 3/19/2007 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### called contr, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, BCC all make-up shall be done, left corr notice
|
Permanent Service | 3/19/2007 | 3/19/2007 | 3/19/2007 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### p/s u/g n ok
|
Application received | | | 3/16/2007 | | DONE |
|
|
|
This permit was created on the web by Therrin Robertson
|