Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE07-00889
StatusFinaled
Name MOUNTAIN POWER ELECT CONTR
Site Address 6624 W EMERALD
Project Name 
Customer Number07-012
ePlanReview 
Description
Electrical Permit - New: construct a new buliding for Capitol Eye. The building will have a 600 amp service and space availabe for lease. Standard lighting and power throughout.Site lighting to include 6 poles. See ELE07-02009 for TI portion of permit
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice ELE9/7/20079/7/20079/11/2007 DONE
First Notice has not been responded to.
First Notice8/24/20078/24/20079/7/2007 DONE
DetailsBob Reichert
Final8/23/20078/24/20078/24/2007APASS
DetailsBob Reichert
randy - late morning please Phone #: ###-#### corrections made, ok to final signed struct card
Final8/22/20078/22/20078/22/2007PCANC
DetailsJack Frank
randy Phone #: ###-#### -please call 1/2 hr prior to inspection corr called 410.15(B)(3)(a) grd terminal shall be at hand hole, note addresses for house and tennant meters shall be correct
Final8/21/20078/22/20078/22/2007AFAIL
DetailsBob Reichert
randy Phone #: ###-#### called, left message,BCC- no structural card to sign nec 250.12 shall remove nonconductive coatings on equipment to be grounded- lite pole, 110.14(A) terminal connections shall be tight to ensure thorough connection- lite pole
Electrical Rough-In8/1/20078/2/20078/2/2007APASS
DetailsBob Reichert
call Randy for morning inspection of site pole lighting.Thanks Phone #: ###-#### Internet Inspection Request from: Loren Ramsey called, u/g for parking lot lights ok to cover
Permanent Service7/19/20077/19/20077/19/2007PPASS
DetailsBob Reichert
randy Phone #: ###-#### Internet Inspection Request from: Loren Ramsey p/s u/g n ok
Electrical Rough-In7/13/20077/13/20077/13/2007PPASS
DetailsWilliam E Thomas
###-#### - randy Note: ceiling
1. drop ceiling ok.
Electrical Rough-In6/6/20076/6/20076/6/2007PPASS
DetailsWilliam E Thomas
randy; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
hard lids ok to cover
Electrical Rough-In6/5/20076/6/20076/6/2007AFAIL
DetailsWilliam E Thomas
randy; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
cieling inspection for hardlids is a do not cover until we see a listing labeling of the caulking that is being squirted into the mc connectors.
Electrical Rough-In6/5/20076/5/20076/5/2007PPASS
DetailsWilliam E Thomas
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt
basement ok, exterior shell walls 1st floor ok
Electrical Rough-In6/1/20076/4/20076/4/2007ANR
DetailsWilliam E Thomas
randy -- in basement; working on-site; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
there are permit issues and they will call for another inspection when they are taken care
Electrical Rough-In4/19/20074/19/20074/19/2007PPASS
DetailsBob Reichert
inspect ug pipe for slab on grade pour Phone #: ###-#### Internet Inspection Request from: Loren Ramsey ok to pour bldg slab only
Electrical Rough-In4/10/20074/11/20074/11/2007APASS
DetailsMike Kinnear
randy- uffer ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok cover ufer ground
Electrical Rough-In4/3/20074/4/20074/3/2007APART
DetailsBob Reichert
lorren - first thing in the morning please - underground ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith contr called and said ready later, 4" has 2 90's and stops at east and south of bldg, power goes straight to west, ok to cover, told to use fines for backfill, no rocks
Electrical Rough-In4/3/20074/3/20074/3/2007PNR
DetailsBob Reichert
jim Note: underground ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no conduit in place yet, called, elect said forgot to postpone
Application received  3/16/2007 DONE
This permit was created on the web by Loren Ramsey