Second Notice ELE | 9/7/2007 | 9/7/2007 | 9/11/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 8/24/2007 | 8/24/2007 | 9/7/2007 | | DONE |
Bob Reichert
|
|
|
|
Final | 8/23/2007 | 8/24/2007 | 8/24/2007 | A | PASS |
Bob Reichert
|
|
|
randy - late morning please Phone #: ###-#### corrections made, ok to final signed struct card
|
Final | 8/22/2007 | 8/22/2007 | 8/22/2007 | P | CANC |
Jack Frank
|
|
|
randy Phone #: ###-#### -please call 1/2 hr prior to inspection corr called 410.15(B)(3)(a) grd terminal shall be at hand hole, note addresses for house and tennant meters shall be correct
|
Final | 8/21/2007 | 8/22/2007 | 8/22/2007 | A | FAIL |
Bob Reichert
|
|
|
randy Phone #: ###-#### called, left message,BCC- no structural card to sign nec 250.12 shall remove nonconductive coatings on equipment to be grounded- lite pole, 110.14(A) terminal connections shall be tight to ensure thorough connection- lite pole
|
Electrical Rough-In | 8/1/2007 | 8/2/2007 | 8/2/2007 | A | PASS |
Bob Reichert
|
|
|
call Randy for morning inspection of site pole lighting.Thanks Phone #: ###-#### Internet Inspection Request from: Loren Ramsey called, u/g for parking lot lights ok to cover
|
Permanent Service | 7/19/2007 | 7/19/2007 | 7/19/2007 | P | PASS |
Bob Reichert
|
|
|
randy Phone #: ###-#### Internet Inspection Request from: Loren Ramsey p/s u/g n ok
|
Electrical Rough-In | 7/13/2007 | 7/13/2007 | 7/13/2007 | P | PASS |
William E Thomas
|
|
|
###-#### - randy Note: ceiling 1. drop ceiling ok.
|
Electrical Rough-In | 6/6/2007 | 6/6/2007 | 6/6/2007 | P | PASS |
William E Thomas
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang hard lids ok to cover
|
Electrical Rough-In | 6/5/2007 | 6/6/2007 | 6/6/2007 | A | FAIL |
William E Thomas
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang cieling inspection for hardlids is a do not cover until we see a listing labeling of the caulking that is being squirted into the mc connectors.
|
Electrical Rough-In | 6/5/2007 | 6/5/2007 | 6/5/2007 | P | PASS |
William E Thomas
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt basement ok, exterior shell walls 1st floor ok
|
Electrical Rough-In | 6/1/2007 | 6/4/2007 | 6/4/2007 | A | NR |
William E Thomas
|
|
|
randy -- in basement; working on-site; Phone #: ###-#### Internet Inspection Request from: Victoria Beall there are permit issues and they will call for another inspection when they are taken care
|
Electrical Rough-In | 4/19/2007 | 4/19/2007 | 4/19/2007 | P | PASS |
Bob Reichert
|
|
|
inspect ug pipe for slab on grade pour Phone #: ###-#### Internet Inspection Request from: Loren Ramsey ok to pour bldg slab only
|
Electrical Rough-In | 4/10/2007 | 4/11/2007 | 4/11/2007 | A | PASS |
Mike Kinnear
|
|
|
randy- uffer ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok cover ufer ground
|
Electrical Rough-In | 4/3/2007 | 4/4/2007 | 4/3/2007 | A | PART |
Bob Reichert
|
|
|
lorren - first thing in the morning please - underground ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith contr called and said ready later, 4" has 2 90's and stops at east and south of bldg, power goes straight to west, ok to cover, told to use fines for backfill, no rocks
|
Electrical Rough-In | 4/3/2007 | 4/3/2007 | 4/3/2007 | P | NR |
Bob Reichert
|
|
|
jim Note: underground ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no conduit in place yet, called, elect said forgot to postpone
|
Application received | | | 3/16/2007 | | DONE |
|
|
|
This permit was created on the web by Loren Ramsey
|