Rough-In Permanent Service | 4/4/2007 | 4/5/2007 | 4/5/2007 | A | PASS |
Jack Frank
|
|
|
cal; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok
|
Electrical Rough-In | 4/4/2007 | 4/4/2007 | 4/4/2007 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 4/4/2007 at 12:49:13 AM. Contact: ###-####. see r/i p/s request
|
Rough-In Permanent Service | 4/4/2007 | 4/4/2007 | 4/4/2007 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 4/4/2007 at 12:50:19 AM. Contact: ###-####. corr. fee due, do not cover 314.43 no nails allowed in plastic boxes, 250.24(A)(1) terminate GEC at neutral bus, 250.28(A)(3) install bond screw, 250.53(B) remove or move grd rod shall be 6ft from other electrodes Footing with rebar is a electrode, BCC complete all makeup all light boxes
|
Reinspection Fee (no hold) | 4/4/2007 | 4/4/2007 | 4/4/2007 | A | DONE |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 4/4/2007 at 12:50:19 AM. Contact: ###-####. fee due corr. posted
|
Electrical Rough-In | 3/19/2007 | 3/19/2007 | 3/19/2007 | P | PART |
Pat Lass
|
|
|
Cal; Phone #: ###-#### Internet Inspection Request from: Stacie Backus U/G Ok
|
Application received | | | 3/19/2007 | | |
|
|
|
|
Issue permit | | | 3/19/2007 | | DONE |
|
|
|
|