Final | 4/4/2007 | 4/6/2007 | 4/6/2007 | P | PASS |
Bob Reichert
|
|
|
electrician- Aaron White Phone #: ###-#### corrections made, ok to final
|
Final | 3/29/2007 | 3/29/2007 | 3/29/2007 | P | FAIL |
Bob Reichert
|
|
|
Resident-Cindy Shotten ###-#### electrician-Aaron White ###-#### Phone #: ###-#### called, left message, left corr notice, nec 352.26&358.26 there shall not be more than 360 degree bends in raceway, 680.22(A)(3) recpt shall be between 10 and 20' of tub, 680.26(A)(5)all metal shall be bonded within 5' horiz and 12' vert above water (gutter)
|
Permanent Service | 3/20/2007 | 3/21/2007 | 3/21/2007 | P | PASS |
Bob Reichert
|
|
|
Work performed by Aaron White. Phone #: ###-#### p/s u/g rec ok
|
Application received | | | 3/20/2007 | | DONE |
|
|
|
This permit was created on the web by Matt Santacruz
|