Final | 6/18/2007 | 6/19/2007 | 6/19/2007 | A | PASS |
Bob Reichert
|
|
|
call to find out how to gain access Phone #: ###-#### Internet Inspection Request from: DJ Carman corr made, ok to final
|
Final | 6/13/2007 | 6/13/2007 | 6/13/2007 | P | FAIL |
Jack Frank
|
|
|
reinspection Phone #: ###-#### Internet Inspection Request from: DJ Carman corr. called 110.3(B) & 422.11(A) shall provide max protection of 25 amps for a/c they changed the W H breaker ,or circuit directory is wrong
|
Reinspection Fee (no hold) | 6/13/2007 | 6/13/2007 | 6/13/2007 | P | DONE |
Jack Frank
|
|
|
reinspection Phone #: ###-#### Internet Inspection Request from: DJ Carman fee due corr. not made new violation created
|
Final | 6/11/2007 | 6/11/2007 | 6/11/2007 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman called, left corr notice, nec 210.52(E) shall install recpt at rear of dwelling, 406.4 recpts shall be securely fastened, 406.5 recpt faceplates shall seat against mounting surface,406.4(D) recpt face shall be flush with or project from faceplate,422.11(A) overcurrent device for a/c shall not exceed mfgr marking on nameplate, 110.3 hall recpt shall operate
|
Permanent Service | 3/30/2007 | 3/30/2007 | 3/30/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### p/s o/h n ok, u/g ok to cover, no time comp down
|
Electrical Rough-In | 3/21/2007 | 3/21/2007 | 3/21/2007 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### ok cover ri
|
Application received | | | 3/20/2007 | | |
|
|
|
|
Issue permit | | | 3/20/2007 | | DONE |
|
|
|
|