Final | 6/18/2007 | 6/19/2007 | 6/19/2007 | A | PASS |
Bob Reichert
|
|
|
call to find out how to gain access Phone #: ###-#### Internet Inspection Request from: DJ Carman corr made, ok to final
|
Final | 6/13/2007 | 6/13/2007 | 6/13/2007 | P | FAIL |
Jack Frank
|
|
|
reinspection Phone #: ###-#### Internet Inspection Request from: DJ Carman corr called 110.3(B) needs 25 amp for a/c not WH, or your circuit directory is not specific as to purpose and use, 334.23 all 3 homes, shall remove NMB from attic accesses and protect as code noted states
|
Reinspection Fee (no hold) | 6/13/2007 | 6/13/2007 | 6/13/2007 | P | DONE |
Jack Frank
|
|
|
reinspection Phone #: ###-#### Internet Inspection Request from: DJ Carman corr. not made new violation cfreated
|
Final | 6/11/2007 | 6/11/2007 | 6/11/2007 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman called, left corr notice, nec 210.52(E) sahll install recpt at rear of dwelling, 210.52(D) shall install recpt upper bath, 110.3 fan shall operate, lower bath, 422.11(A) overcurrent for a/c shall not exceed mfgrs marking
|
Permanent Service | 3/30/2007 | 3/30/2007 | 3/30/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### p/s o/h n ok, u/g ok to cover, no time comp down
|
Electrical Rough-In | 3/21/2007 | 3/21/2007 | 3/21/2007 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### ok cover ri
|
Application received | | | 3/20/2007 | | |
|
|
|
|
Issue permit | | | 3/20/2007 | | DONE |
|
|
|
|