Final | 4/2/2007 | 4/3/2007 | 4/3/2007 | P | PASS |
Bob Reichert
|
|
|
bryan ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corrections made, ok to final
|
Final | 3/29/2007 | 3/29/2007 | 3/29/2007 | P | FAIL |
Bob Reichert
|
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Victoria Beall left corr notice, nec 408.4 all circuits shall be labelled at panel and be clear and concise, 334.30 nm cable shall be stapled within 12" of panel, 210.52(D) gfci recpt shall be installed within 3' of basin in bath
|
Application received | | | 3/23/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 3/23/2007 | | DONE |
|
|
|
|