Information based on query as of Sunday, July 7, 2024.
Permit Information
Permit NumberELE07-01017
StatusFinaled
Name TOTAL ELECTRIC INC
Site Address 1716 S ROOSEVELT ST
Project Name 
Customer Number 
ePlanReview 
Description
3/27/07/ rough in 2nd floor- office space, fed sub panels and wired recepts and lights/initial cert of value $2,000/mls ///final value is $8000 per faxed document 6-5-07ps
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice ELE5/29/20075/29/20076/5/2007 DONE
Second Notice has not been responded to.
Second Notice ELE5/14/20075/14/20075/29/2007 DONE
First Notice has not been responded to.
First Notice4/25/20074/25/20075/14/2007 DONE
DetailsBob Reichert
Final4/25/20074/25/20074/25/2007PPASS
DetailsBob Reichert
Justin; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corrections made, ok to final, signed card
Final4/24/20074/25/20074/25/2007APART
DetailsBob Reichert
justin; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover clgs, left corr notice, nec 110.12(A) close openings, 408.4 circuit directory shall be done, 110.3 shall fix recpts and supply power to office
Conference4/19/20074/20/20074/20/2007ADONE
DetailsBob Reichert
ryan; Phone #: ###-#### Internet Inspection Request from: Victoria Beall talked about walls and ceilings, said no lv shall lay on grid, need grid installed and fixtures installed for inspection
Electrical Rough-In4/17/20074/17/20074/17/2007PFAIL
DetailsBob Reichert
ryan - ceiling ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called contr, ceiling still has nm cable, some tiles installed, can't see if correct, need to build grid in parts and install fixtures, explained that could do all rather than 2 inspections if ready
Conference4/6/20074/9/20074/9/2007ADONE
DetailsWilliam E Thomas
ryan - first thing in the morning please ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
talked about romex in a commercial space
Electrical Rough-In3/27/20073/28/20073/28/2007APART
DetailsMike Kinnear
ryan--- ###-#### ok cover walls only note romex needs to be removed & the low voltage cable needs to be cleaned up. call t/w electrical contractor
Application received  3/27/2007  
Issue PAID IN FULL permit  3/27/2007