Final | 8/7/2007 | 8/8/2007 | 8/8/2007 | A | PART |
Bob Reichert
|
|
|
jim Phone #: ###-#### met contr, ok to final, signed occ card
|
Electrical Rough-In | 7/20/2007 | 7/23/2007 | 7/23/2007 | P | PASS |
Bob Reichert
|
|
|
jim - ceiling Phone #: ###-#### corr made, ok to cover ceiling
|
Electrical Rough-In | 7/19/2007 | 7/20/2007 | 7/20/2007 | A | FAIL |
Bob Reichert
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called, left corr notice, nec 300.11(A) individual support wires shall be secured at both ends. Cables and raceways shall not be supported by ceiling grids. 330.30(B) mc cable shall be secured within 12" of each termination
|
Electrical Rough-In | 7/18/2007 | 7/18/2007 | 7/18/2007 | P | FAIL |
Mike Kinnear
|
|
|
bo - ceiling Phone #: ###-#### ceiling tile installed unable to do inspection reiinspection fee called contractor
|
Reinspection Fee (no hold) | 7/18/2007 | 7/18/2007 | 7/18/2007 | P | NR |
Mike Kinnear
|
|
|
bo - ceiling Phone #: ###-#### ceiling tile installed reinspection fee
|
Electrical Rough-In | 4/20/2007 | 4/20/2007 | 4/20/2007 | P | PASS |
Bob Reichert
|
|
|
Jim possible between 2 or 3 they''''re driving back to Boise today.; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ric ok walls only
|
Electrical Rough-In | 4/19/2007 | 4/20/2007 | 4/20/2007 | A | NR |
Mike Kinnear
|
|
|
jim ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith framers moving walls electrical removed conf called support within 1ft of boxes mc cable, 1 1/4inch from edge of framing members, & can not support conduits or cables on other conduits or cables.
|
Application received | | | 3/30/2007 | | |
|
|
|
|
Issue permit | | | 3/30/2007 | | DONE |
|
|
|
|
Telephone call | | | | | |
|
|
|
tlk to chuck of argus elec ###-#### about the difference of value of cert he will call be back 9:30 am
|