Temporary Service | 7/3/2007 | 7/3/2007 | 7/3/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham corrections made t/s o/h n ok
|
Temporary Service | 7/2/2007 | 7/2/2007 | 7/2/2007 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham corrections not made
|
Temporary Service | 3/30/2007 | 4/2/2007 | 4/2/2007 | A | FAIL |
Bob Reichert
|
|
|
Brandon; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called, left corr notice, nec 404.8 center of upper bkr handle shall not be over 6"- 7" high, 408.4 shall provide circuit directory, 312.5 abrasion protection shall be provided for all conductors entering enclosures
|
Application received | | | 3/30/2007 | | |
|
|
|
|
Issue permit | | | 3/30/2007 | | DONE |
|
|
|
|