Final | 8/8/2008 | 8/8/2008 | 8/8/2008 | P | PASS |
Mike Kinnear
|
|
|
permit taken over by ele08-02209
|
Electrical Rough-In | 4/2/2007 | 4/3/2007 | 4/3/2007 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 4/2/2007 at 8:29:11 PM. Contact: ###-####. ok cover ri
|
Electrical Rough-In | 4/1/2007 | 4/2/2007 | 4/2/2007 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### corr. called 300.14 6" free length all locations, 110/14(B) loose crimp sleeves equip. grds, 300.4 (A)(1&(D) nail plates and 11/4" cables parallel to studs, 210.11(C)(2) all recepts in laundry shall be on laundry rm 20 amp circuit, 314.43 remove screw from inside of box in front soofit
|
Permanent Service | 4/2/2007 | 4/2/2007 | 4/2/2007 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### p/s u/g new ok
|
Application received | | | 4/1/2007 | | DONE |
|
|
|
This permit was created on the web by Robert Waite
|