Final | 7/6/2007 | 7/6/2007 | 7/6/2007 | P | PASS |
Mike Kinnear
|
|
|
Please let Luke know if this does not pass! Phone #: ###-#### Internet Inspection Request from: KATHY WEIL corrections made ok final
|
Final | 7/2/2007 | 7/3/2007 | 7/3/2007 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: KATHY WEIL called, left corr notice, nec 210.52(A)(2) shall install recpt in 2' wall in north bedroom, 352.30(A) shall strap rnc at panel within 3' of termination, 110.22 shall label garage disconnect and tell off-on on label, 410.8(A) closet light below stairs shall be 12" from shelving to edge of fixture, 210.8(A)(3) front and bath gfci shall operate correctly, 110.3(B) listed equip shall be installed per instructions i.e. kitchen and laundry recpts have open neutrals
|
Rough-In Permanent Service | 4/9/2007 | 4/11/2007 | 4/11/2007 | A | PASS |
Bob Reichert
|
|
|
Let Luke know if this doesn''t pass please! Phone #: ###-####called contr about recpts, ric ok, p/s u/g n ok, ok to backfill
|
Electrical Rough-In | 4/10/2007 | 4/10/2007 | 4/10/2007 | P | PART |
Bob Reichert
|
|
|
Reinspect Ufer Phone #: ###-#### gec ok to pour
|
Electrical Rough-In | 4/9/2007 | 4/10/2007 | 4/10/2007 | P | CANC |
Bob Reichert
|
|
|
Concrete incasement inspection,thank you! Phone #: ###-#### Inspection cancelled from web by: KATHY WEIL
|
Electrical Rough-In | 4/9/2007 | 4/10/2007 | 4/10/2007 | A | FAIL |
Bob Reichert
|
|
|
Ufer inspection,thank you! Phone #: ###-#### called, gec not tied down, not cleaned
|
Electrical Rough-In | 4/8/2007 | 4/9/2007 | 4/9/2007 | A | PASS |
Bob Reichert
|
|
|
This inspection is actually for the conduit from the house to the garage so they can get it backfilled. Phone #: ###-#### ok to cover u/g only
|
Rough-In Permanent Service | 4/5/2007 | 4/9/2007 | 4/8/2007 | A | CANC |
Bob Reichert
|
|
|
Please call Luke if this inspections fails.
Thanks Bob:) Phone #: ###-#### Inspection cancelled from web by: KATHY WEIL
|
Application received | | | 4/5/2007 | | DONE |
|
|
|
This permit was created on the web by KATHY WEIL
|