Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE07-01209
StatusFinaled
Name TOWN & COUNTRY ELECTRIC
Site Address 11875 W PRESIDENT DR
Project Name 
Customer Number 
ePlanReview 
Description
Temporary Power Pole: Install temp pole
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice ELE5/14/20075/14/20075/15/2007 DONE
Second Notice has not been responded to.
Second Notice ELE4/24/20074/24/20075/14/2007 DONE
First Notice has not been responded to.
Second Notice ELE4/24/20074/24/20075/14/2007 DONE
First Notice has not been responded to.
First Notice4/13/20074/13/20074/24/2007 DONE
DetailsJack Frank
First Notice4/13/20074/13/20074/24/2007 DONE
DetailsJack Frank
Final4/13/20074/13/20074/13/2007PPASS
DetailsJack Frank
Ready for reinspect. Contact is Brian Phone #: ###-#### x0000 ok corr. made
Temporary Service4/13/20074/13/20074/13/2007PPASS
DetailsJack Frank
Ready for reinspect. Contact is Brian Phone #: ###-#### x0000 t/s u/g new ok
Temporary Service4/10/20074/11/20074/11/2007AFAIL
DetailsJack Frank
Temp pole is near the xfmer at the south end of the building 100'' east of Sage Construction job trailer. Phone #: ###-#### x0000 corr. called 110.3(B) install manufactures tie bar between neutral buses, use manufactures breakers only, 110.14(A) tighten all screws at bond bushing, 110.12(C) clean all dirt from T/S, 250.64(B) protect #8 GEC, 312.5 use conn. for GEC
Reinspection Fee (no hold)4/11/20074/11/20074/11/2007ADONE
DetailsJack Frank
Temp pole is near the xfmer at the south end of the building 100'' east of Sage Construction job trailer. Phone #: ###-#### x0000 fee due corr
Application received  4/9/2007 DONE
This permit was created on the web by Tawnya McKinney