Rough-In Permanent Service | 5/17/2007 | 5/18/2007 | 5/18/2007 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Justin Yount ok cover ri p/s u/g n ok note no under ground between house & garage has been done
|
Rough-In Permanent Service | 5/15/2007 | 5/16/2007 | 5/16/2007 | A | FAIL |
Bob Reichert
|
|
|
Between Raymond and Liberty on Poplar. Phone #: ###-#### Internet Inspection Request from: Justin Yount called contr, left corr notice, nec 230.2 a building shall be supplied by only 1 service, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 314.16 boxes shall have free space for conductors, BCC all make-up shall be done, all u/g shall be inspected prior to cover, service will be done with ri
|
Application received | | | 4/11/2007 | | DONE |
|
|
|
This permit was created on the web by Justin Yount
|