Final | 6/12/2007 | 6/12/2007 | 6/12/2007 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/12/2007 at 6:57:28 AM. Contact: ###-####. ok called be specific circuit directory
|
Electrical Rough-In | 4/13/2007 | 4/13/2007 | 4/13/2007 | P | PASS |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 4/13/2007 at 8:37:35 AM. Contact: ###-####. ri ok
|
Rough-In Permanent Service | 4/12/2007 | 4/12/2007 | 4/12/2007 | P | FAIL |
Jack Frank
|
|
|
###-#### greg corr. fee due see added p/s 300.4(A)(1) nail plates inside outside edges everywhere, 314.17 (C) replace 2 gang outside outlet boxes with factory clamps broken out, 250.53(B) remove or move grd rod shall be 6ft from foundation (concrete encased electrode called
|
Permanent Service | 4/12/2007 | 4/12/2007 | 4/12/2007 | P | PASS |
Jack Frank
|
|
|
###-#### greg p/s u/g new ok
|
Reinspection Fee (no hold) | 4/12/2007 | 4/12/2007 | 4/12/2007 | P | DONE |
Jack Frank
|
|
|
###-#### greg fee due corr.
|
Application received | | | 4/12/2007 | | |
|
|
|
|
Issue permit | | | 4/12/2007 | | DONE |
|
|
|
|