Final | 1/10/2008 | 1/10/2008 | 1/10/2008 | P | PASS |
Bob Reichert
|
|
|
kelly Phone #: ###-#### ok to final, corrections made
|
Final | 1/9/2008 | 1/9/2008 | 1/9/2008 | P | FAIL |
Bob Reichert
|
|
|
kelly Phone #: ###-#### met owner, correction not made, open ground on gfci, loose recpt west wall
|
Final | 1/8/2008 | 1/8/2008 | 1/8/2008 | P | FAIL |
Bob Reichert
|
|
|
kelly Phone #: ###-#### called , 210.8(A)(2) receptacles shall be gfci protected
|
Electrical Rough-In | 10/17/2007 | 10/17/2007 | 10/17/2007 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 10/17/2007 at 7:52:03 AM. Contact: ###-####. ok cover ri
|
Electrical Rough-In | 10/15/2007 | 10/15/2007 | 10/15/2007 | P | FAIL |
Bob Reichert
|
|
|
kelly Note:please call 1/2 hr prior Phone #: ###-#### corrections not all made, shall provide 6" free conductor at all boxes, met owners father who seems to be doing the work, told to call when fixed
|
Permanent Service | 10/3/2007 | 10/3/2007 | 10/3/2007 | P | CANC |
Bob Reichert
|
|
|
patrick Phone #: ###-#### wrong inspection request, owner hired contractor to change service, see ele07-03419
|
Electrical Rough-In | 9/28/2007 | 9/28/2007 | 9/28/2007 | P | FAIL |
Bob Reichert
|
|
|
kelly Phone #: ###-#### called, left corr notice, nec 250.28(B) shall use bonding jumper in panel, 334.30 nm cable shall be stapled within 12" of panel and not on edge, 314.17(C) nm cable shall be stapled within 8" of single gang box and not stapled on edge, 300.14 at least 6" free conductor shall be provided in each box with sheathing cut to 1/4" of cable entry,250.80 metal boxes shall be grounded,250.126(1) green ground screw shall be provided
|
Electrical Rough-In | 9/13/2007 | 9/13/2007 | 9/13/2007 | P | PASS |
Bob Reichert
|
|
|
raina - trench Phone #: ###-#### u/g only ok to cover from house to new garage
|
Electrical Rough-In | 8/17/2007 | 8/17/2007 | 8/17/2007 | P | FAIL |
Bob Reichert
|
|
|
trench inspection call first as late as possible; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called, left correction notice, nec there shall not be more than 360 degree total bend in rnc, 300.5 min burial depth by fence and garage shall be 18" to top of conduit
|
Application received | | | 4/25/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 4/25/2007 | | DONE |
|
|
|
|