Permit NumberELE07-01468
StatusFinaled
Name JAMISON KELLY W
Site Address 12142 W LA PAN DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/10/20081/10/20081/10/2008PPASS
DetailsBob Reichert
kelly Phone #: ###-#### ok to final, corrections made
Final1/9/20081/9/20081/9/2008PFAIL
DetailsBob Reichert
kelly Phone #: ###-#### met owner, correction not made, open ground on gfci, loose recpt west wall
Final1/8/20081/8/20081/8/2008PFAIL
DetailsBob Reichert
kelly Phone #: ###-#### called , 210.8(A)(2) receptacles shall be gfci protected
Electrical Rough-In10/17/200710/17/200710/17/2007PPASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 10/17/2007 at 7:52:03 AM. Contact: ###-####. ok cover ri
Electrical Rough-In10/15/200710/15/200710/15/2007PFAIL
DetailsBob Reichert
kelly Note:please call 1/2 hr prior Phone #: ###-#### corrections not all made, shall provide 6" free conductor at all boxes, met owners father who seems to be doing the work, told to call when fixed
Permanent Service10/3/200710/3/200710/3/2007PCANC
DetailsBob Reichert
patrick Phone #: ###-#### wrong inspection request, owner hired contractor to change service, see ele07-03419
Electrical Rough-In9/28/20079/28/20079/28/2007PFAIL
DetailsBob Reichert
kelly Phone #: ###-#### called, left corr notice, nec 250.28(B) shall use bonding jumper in panel, 334.30 nm cable shall be stapled within 12" of panel and not on edge, 314.17(C) nm cable shall be stapled within 8" of single gang box and not stapled on edge, 300.14 at least 6" free conductor shall be provided in each box with sheathing cut to 1/4" of cable entry,250.80 metal boxes shall be grounded,250.126(1) green ground screw shall be provided
Electrical Rough-In9/13/20079/13/20079/13/2007PPASS
DetailsBob Reichert
raina - trench Phone #: ###-#### u/g only ok to cover from house to new garage
Electrical Rough-In8/17/20078/17/20078/17/2007PFAIL
DetailsBob Reichert
trench inspection call first as late as possible; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called, left correction notice, nec there shall not be more than 360 degree total bend in rnc, 300.5 min burial depth by fence and garage shall be 18" to top of conduit
Application received  4/25/2007  
Issue PAID IN FULL permit  4/25/2007 DONE