Final | 6/12/2007 | 6/12/2007 | 6/12/2007 | P | PASS |
Jack Frank
|
|
|
darren; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok survey posted called 408.4 panel schedule be specific purpose and use, 406.4 loose recepts master bath
|
Electrical Rough-In | 4/27/2007 | 4/27/2007 | 4/27/2007 | P | PASS |
Jack Frank
|
|
|
darin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok corr made
|
Electrical Rough-In | 4/26/2007 | 4/27/2007 | 4/27/2007 | A | FAIL |
Jack Frank
|
|
|
darren ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr not made met with contr.
|
Reinspection Fee (no hold) | 4/27/2007 | 4/27/2007 | 4/27/2007 | P | DONE |
Jack Frank
|
|
|
darren ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith fee due corr not made
|
Permanent Service | 4/27/2007 | 4/27/2007 | 4/27/2007 | P | PASS |
Jack Frank
|
|
|
darren ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok p/s u/g new ok
|
Electrical Rough-In | 4/25/2007 | 4/26/2007 | 4/26/2007 | A | FAIL |
Jack Frank
|
|
|
darin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. do not cover posted called300.4 nail plates 11/4" 334.23 protect romex at attic access, 312.5 conn for low volt cables, and staple, 334.30 & 314.17(C) staple romex within 8" of boxes, 314.20 outside boxes shall be flush with siding, BCC makeup all outside boxes
|
Application received | | | 4/25/2007 | | |
|
|
|
|
Issue permit | | | 4/25/2007 | | DONE |
|
|
|
|