Final | 10/16/2008 | 10/16/2008 | 10/16/2008 | P | PASS |
Bob Reichert
|
|
|
chris Phone #: ###-#### ok to final,
|
Final | 1/28/2008 | 1/28/2008 | 1/28/2008 | P | CANC |
Bob Reichert
|
|
|
Chris ###-#### wrong type request, see ri
|
Electrical Rough-In | 1/28/2008 | 1/28/2008 | 1/28/2008 | P | PASS |
Bob Reichert
|
|
|
Chris ###-#### corrections made, ric ok
|
Final | 11/15/2007 | 11/20/2007 | 11/20/2007 | P | CANC |
Bob Reichert
|
|
|
chris Phone #: ###-#### see ri
|
Electrical Rough-In | 11/20/2007 | 11/20/2007 | 11/20/2007 | P | FAIL |
Bob Reichert
|
|
|
chris Phone #: ###-#### met owner, cjecked for free length of conductor because devices installed, that part ok, but corrections needed are: nec 210.8(A)(1)&(2) garage and bathroom shall have gfci receptacles installed, 210.70(A)(2) shall provide switched lighting outlet at man door, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 250 and BCC shall tie grounds together in boxes with more than 1 device
|
Permanent Service | 8/28/2007 | 9/4/2007 | 9/4/2007 | P | PASS |
Bob Reichert
|
|
|
Chris; Phone #: ###-#### Internet Inspection Request from: Hattie James met owner, check sub-panels for ground isolation at ri, p/s u/g rec ok
|
Electrical Rough-In | 6/4/2007 | 6/4/2007 | 6/4/2007 | P | PASS |
Mike Kinnear
|
|
|
Underground conduit pre-backfill inspection; Chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok cover under ground conduit
|
Electrical Rough-In | 5/21/2007 | 5/21/2007 | 5/21/2007 | P | PART |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Victoria Beall met owner to look at concrete encased electrode, there is re-bar on east side shop that is ok; will connect copper to rebar for service
|
Conference | 4/30/2007 | 5/1/2007 | 5/1/2007 | A | DONE |
Bob Reichert
|
|
|
Chris ###-#### met owner to talk about service for new garage and sub-feed to house
|
Application received | | | 4/30/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 4/30/2007 | | |
|
|
|
|