Permit Information
Permit NumberELE07-01598
StatusFinaled
Name KENDALL ELECTRIC
Site Address 1455 S CAPITOL BLVD
Project Name 
Customer Number2552
ePlanReview 
Description
Electrical Permit - New: MAIN PERMIT FOR COMPLETE ELECTRICAL INSTALLATIONS FOR THE TOWNPLACE,BOISE HOTEL. DEVICES, SWITCHES, LIGHTING, ETC.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice2/4/20082/4/20082/13/2008 DONE
DetailsPat Lass
This permit finaled on the web by Barry Kendall
Final2/1/20082/4/20082/4/2008APASS
DetailsPat Lass
Scheduled by a contractor via Hello! on 2/1/2008 at 11:01:24 AM. Contact: ###-####.
Final1/22/20081/23/20081/23/2008PPART
DetailsPat Lass
Scheduled by a contractor via Hello! on 1/22/2008 at 3:41:46 PM.
signed T/O
reidentify white wires used for other than neutrals
insure electrical and mechanical continuity to gutters
properly size pullbox/gutter and correct for deration
correct fuses for p-tac's and a/c units
bond pool room vents
strap flex by panel "P"
ground pole light bases and insure proper overcurrent
Final1/9/20081/10/20081/10/2008APART
DetailsPat Lass
Scheduled by a contractor via Hello! on 1/9/2008 at 9:54:57 AM. Contact: ###-####.
first floor ok
Final1/8/20081/9/20081/9/2008ACANC
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 1/8/2008 at 12:51:34 PM. canc per 324
Final1/7/20081/8/20081/8/2008PPART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 1/7/2008 at 5:06:54 PM. 2nd floor hall, ceilings and rooms ok to final
Final1/3/20081/3/20081/3/2008APART
DetailsBob Reichert
ok to final 4th floor rooms only
Final1/2/20081/3/20081/3/2008APART
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 1/2/2008 at 4:04:04 PM. Contact: ###-####. ok cover ceiling 3rd floor ok final 3rd floor rms
Final12/31/200712/31/200712/31/2007AFAIL
DetailsJack Frank
helped 370 see his response
Final12/29/200712/31/200712/31/2007AFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 12/29/2007 at 7:30:41 AM. Contact: ###-####. wrong length disposal cords, arc fault circuits not correct per room layout, switch plates not flush, met electrician, all 4th floor comments, he has list
Electrical Rough-In12/26/200712/27/200712/27/2007ACANC
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 12/26/2007 at 1:52:09 PM. wrong permit number
Electrical Rough-In11/13/200711/13/200711/13/2007PPART
DetailsMike Kinnear
RE-INSPECTION FOR T-GRID IN CORRIDOR ON 4TH FLOOR - TOWNPLACE SUITES HOTEL ok cover t-grid 4th floor only

THANKS Phone #: ###-#### Internet Inspection Request from: Barry Kendall
Reinspection Fee (no hold)11/13/200711/13/200711/13/2007ANR
DetailsBob Reichert
see comment
Electrical Rough-In11/12/200711/13/200711/13/2007ANR
DetailsBob Reichert
T-GRID COVER INSPECTION FOR THE CORRIDOR ON THE 4TH FLOOR. TOWNPLACE SUITES HOTEL.

THANK YOU Phone #: ###-#### Internet Inspection Request from: Barry Kendall met electrician, wanted inspection for thursday, not today
Electrical Rough-In10/24/200710/26/200710/26/2007PCANC
DetailsWilliam E Thomas
LOBBY AREA - TOWNPLACE SUITES HOTEL

THANKS Phone #: ###-#### Internet Inspection Request from: Barry Kendall
. 1. as noted on prints ok for cover. .
Electrical Rough-In10/18/200710/19/200710/19/2007APART
DetailsMike Kinnear
PLEASE INSPECT 1/2 OF THE LOBBY AREA. TOWNPLACE SUITES HOTEL. THANKS Phone #: ###-#### Internet Inspection Request from: Barry Kendall ok cover walls & hard lid ceilings anop
Electrical Rough-In10/3/200710/3/200710/3/2007PPASS
DetailsMike Kinnear
UNDERGROUND PARKING LOT INSPECTION - P.M. PLEASE Phone #: ###-#### Internet Inspection Request from: Barry Kendall ok cover under ground conduit for site lighting
Electrical Rough-In9/14/20079/14/20079/14/2007PPART
DetailsMike Kinnear
READY FOR RE-INSPECTION. 1ST FLOOR GUEST ROOMS - TOWNPLACE SUITES HOTEL. THANKS. Phone #: ###-#### Internet Inspection Request from: Barry Kendall ok cover guest rms walls, ceilings, & corador walls only anop
Electrical Rough-In9/12/20079/12/20079/12/2007PFAIL
DetailsBob Reichert
READY FOR RE-INSPECTION @ TOWNPLACE SUITES - 1st FLOOR GUEST ROOMS. THANKS Phone #: ###-#### Internet Inspection Request from: Barry Kendall met elect, left corr notice, nec 110.26(F)(1) there shall be drip protection over panels, 362.30(A) ent shall be secured within 3' of termination and every 3', 330.30(B) mc cable shall be secured within 12" of box and every 6', BCC all make-up shall be done
Electrical Rough-In9/6/20079/6/20079/6/2007PNR
DetailsBob Reichert
Danny 1st floor guest rooms Phone #: ###-#### rooms not ready, met elect told to have all work done before call for cover, i.e. smurf for low voltage, fire alarm piping, covers on boxes, strapping for panel conduit, drip shields over panels, some rooms appear to need extra receptacles installed
Permanent Service9/6/20079/6/20079/6/2007PPASS
DetailsBob Reichert
met elect, talked with 412 and he had looked at corrections that 315 wrote and they were ok. Looked at u/g per ri inspection this date, put sticker on switchgear, p/s u/g n ok, there is not a meter socket on transformer
Electrical Rough-In9/6/20079/6/20079/6/2007PPASS
DetailsBob Reichert
looked at u/g coming out of building going to transformer, said ok to cover . Depth and spacing ok
Electrical Rough-In9/5/20079/6/20079/6/2007APART
DetailsWilliam E Thomas
wayne - underground conduit at town place suites Phone #: ###-####
. 1. depth by the transformer ok. they will uncover the run at the building for inspection also.
Permanent Service8/24/20078/24/20078/24/2007PFAIL
DetailsMike Kinnear
wayne Phone #: ###-####Note: for east evelator and main gear there is no inspection for under ground conduit to the service equipment.
Permanent Service8/22/20078/23/20078/23/2007AFAIL
DetailsJack Frank
wayne Phone #: ###-####Note: main gear east elevator corr grd water within 5ft needs bell ends for u/g pvc, plastic or listed conn for GEC, terminate all GEC to neutral bus
Reinspection Fee (no hold)8/23/20078/23/20078/23/2007ADONE
DetailsJack Frank
wayne Phone #: ###-####Note: main gear east elevator fee due corr
Electrical Rough-In8/23/20078/23/20078/23/2007APART
DetailsJack Frank
wayne Phone #: ###-####Note: main gear east elevator walls and hard ceilings elevator rm
Electrical Rough-In8/3/20078/6/20078/6/2007APART
DetailsMike Kinnear
wayne - 2nd floor rooms and hallways, wall cover inspection Phone #: ###-#### ok cover walls ceiling & corador walls anop ok cover equipment elevator rm 1st floor west end
Electrical Rough-In7/23/20077/24/20077/24/2007APART
DetailsBob Reichert
wayne - cover; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang marked plans 3rd floor stating stairwells only ok to cover
Electrical Rough-In6/29/20077/2/20077/2/2007APART
DetailsMike Kinnear
wayne - 3rd fl wall cover; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok cover walls & ceiling rooms only & corador walls third floor anop
Electrical Rough-In6/11/20076/11/20076/11/2007PPART
DetailsJack Frank
josh - 4th floor; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
ok anop
Application received  5/3/2007 DONE
This permit was created on the web by Barry Kendall