Second Notice ELE | 8/8/2007 | 8/8/2007 | 8/10/2007 | | DONE |
|
|
|
This permit finaled on the web by Monty Adkinson
|
First Notice | 7/16/2007 | 7/16/2007 | 8/8/2007 | | DONE |
Bob Reichert
|
|
|
|
Final | 7/16/2007 | 7/16/2007 | 7/16/2007 | P | PASS |
Bob Reichert
|
|
|
MONTY Phone #: ###-#### ok to final, signed occ card
|
Electrical Rough-In | 7/16/2007 | 7/16/2007 | 7/16/2007 | P | PASS |
Bob Reichert
|
|
|
MONTY NOTE: UNDERGROUND Phone #: ###-#### u/g ok to cover
|
Final | 7/14/2007 | 7/16/2007 | 7/16/2007 | A | FAIL |
Jack Frank
|
|
|
Final inspection for inside, sign raceways exposed for inspector to see in flower bed Phone #: ###-#### Internet Inspection Request from: Monty Adkinson corr fee due 210.8(B)(2) needs gfci for kit. 300.5 needs required depth for all conduits flower beb
|
Reinspection Fee (no hold) | 7/16/2007 | 7/16/2007 | 7/16/2007 | A | DONE |
Jack Frank
|
|
|
Final inspection for inside, sign raceways exposed for inspector to see in flower bed Phone #: ###-#### Internet Inspection Request from: Monty Adkinson fee due job not ready
|
Electrical Rough-In | 7/5/2007 | 7/5/2007 | 7/5/2007 | A | PASS |
Bob Reichert
|
|
|
Grid inspection for cover, wires are secured on both ends. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson corrections made, ok to cover ceiling only
|
Electrical Rough-In | 7/3/2007 | 7/3/2007 | 7/3/2007 | P | FAIL |
Bob Reichert
|
|
|
Grid inspection for cover Phone #: ###-#### Internet Inspection Request from: Monty Adkinson corrections not made, called contractor, left message, read passge on independent support wires, signed corr notice 2nd time
|
Reinspection Fee (no hold) | 7/3/2007 | 7/3/2007 | 7/3/2007 | P | FAIL |
Bob Reichert
|
|
|
Grid inspection for cover Phone #: ###-#### Internet Inspection Request from: Monty Adkinson see failed inspection
|
Electrical Rough-In | 7/3/2007 | 7/3/2007 | 7/3/2007 | A | FAIL |
Bob Reichert
|
|
|
need grid inspection for ceiling cover Phone #: ###-#### Internet Inspection Request from: Monty Adkinson corrections not made, fee due
|
Reinspection Fee (no hold) | 7/3/2007 | 7/3/2007 | 7/3/2007 | P | FAIL |
Bob Reichert
|
|
|
need grid inspection for ceiling cover Phone #: ###-#### Internet Inspection Request from: Monty Adkinson corrections not made
|
Electrical Rough-In | 7/2/2007 | 7/2/2007 | 7/2/2007 | P | FAIL |
Bob Reichert
|
|
|
Need grid cover inspection Phone #: ###-#### Internet Inspection Request from: Monty Adkinson called, left corr notice, per nec 300.11(A) and BCC there shall be no cable on grid
|
Permanent Service | 6/26/2007 | 6/26/2007 | 6/26/2007 | A | PASS |
Bob Reichert
|
|
|
need okay to connect, meters are suite 130 A, suite 130 B, 150A breakers Phone #: ###-#### Internet Inspection Request from: Monty Adkinson p/s exst meter pak, 2 meters req'd, n ok
|
Electrical Rough-In | 5/22/2007 | 5/22/2007 | 5/22/2007 | P | PASS |
William E Thomas
|
|
|
Need rough inspection for wall cover in space. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson 1. walls, hard lids, and soffits ok to cover. 2. no feeders pulled to the panels yet.
|
Electrical Rough-In | 5/4/2007 | 5/4/2007 | 5/4/2007 | A | PASS |
Bob Reichert
|
|
|
Need cover inspection on floor receptacles in space Phone #: ###-#### Internet Inspection Request from: Monty Adkinson u/g ok to cover
|
Owner Supplied Equipment | | | 5/4/2007 | | |
|
|
|
|
Application received | | | 5/4/2007 | | DONE |
|
|
|
This permit was created on the web by Monty Adkinson
|