Final | 8/20/2009 | 8/21/2009 | 8/21/2009 | A | PASS |
Doug A Poedy
|
|
|
chris Phone #: ###-####. Ok final.
|
Final | 8/17/2009 | 8/18/2009 | 8/18/2009 | A | NH |
Doug A Poedy
|
|
|
chris Phone #: ###-####. Left notification on door.
|
Change Status to I | | | 8/10/2009 | | DONE |
|
|
|
|
Rough-In Permanent Service | 8/22/2007 | 8/22/2007 | 8/22/2007 | P | PASS |
Bob Reichert
|
|
|
chris Phone #: ###-#### corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 8/16/2007 | 8/16/2007 | 8/16/2007 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### called contr, only part corrections made, didn't mean to call for inspection yet, see edited corr notice on door, only 1 1/4" taken care of
|
Rough-In Permanent Service | 8/14/2007 | 8/14/2007 | 8/14/2007 | P | FAIL |
Bob Reichert
|
|
|
Chris; Phone #: ###-#### Internet Inspection Request from: Hattie James called, left corr notice, nec 314.20 in walls of combustible material, boxes shall be flush with or project from finished surface, 110.26(F)(1)(a) there shall be no foreign ducts in dedicated panel space, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.24 bend radius of nm cable shall be 5 times diameter of cable, 250.80 house panel enclosure shall be grounded, BCC address shall be posted
|
Conference | 5/8/2007 | 5/9/2007 | 5/9/2007 | A | CANC |
Bob Reichert
|
|
|
Chris this is for a conduet inspection; Phone #: ###-#### Internet Inspection Request from: Darla Downs wrong type request, see ri
|
Electrical Rough-In | 5/9/2007 | 5/9/2007 | 5/9/2007 | A | PASS |
Bob Reichert
|
|
|
Chris this is for a conduet inspection; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok to cover u/g house to garage
|
Application received | | | 5/8/2007 | | |
|
|
|
|
Issue permit | | | 5/8/2007 | | |
|
|
|
|