Final | 5/13/2007 | 5/14/2007 | 5/14/2007 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ron Zimmerman ok see added p/s
|
Permanent Service | 5/14/2007 | 5/14/2007 | 5/14/2007 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ron Zimmerman p/s o/h new ok
|
Permanent Service | 5/11/2007 | 5/11/2007 | 5/11/2007 | P | FAIL |
Jack Frank
|
|
|
ron ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see added r/i corr called 250.119&550.33 ID equip grd green both ends, 312.5 needs conn for GEC, 250.56 needs 2 grd rods
|
Electrical Rough-In | 5/11/2007 | 5/11/2007 | 5/11/2007 | P | PASS |
Jack Frank
|
|
|
ron ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith trench ok
|
Application received | | | 5/11/2007 | | |
|
|
|
|
Issue permit | | | 5/11/2007 | | DONE |
|
|
|
|