Final | 7/5/2007 | 7/6/2007 | 7/6/2007 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok final
|
Final | 7/3/2007 | 7/5/2007 | 7/5/2007 | P | CANC |
Bob Reichert
|
|
|
gena - please call 1/2 hr prior to inspection Phone #: ###-#### called, left message, called contractor, he did not call for inspection, he said he would check on who called and set up an inspection. Homeowner called after 370 out of area and out of time to say they called for inspection. 370 told them that the elect contractor would schedule and call for final.
|
Final | 6/26/2007 | 6/27/2007 | 6/27/2007 | A | NH |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack called contr, nh, dog in back yard
|
Electrical Rough-In | 6/12/2007 | 6/13/2007 | 6/13/2007 | A | PASS |
Mike Kinnear
|
|
|
POOL LIGHT POTTING COMPOUND Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok light potting
|
Electrical Rough-In | 6/4/2007 | 6/5/2007 | 6/5/2007 | A | PASS |
William E Thomas
|
|
|
equipotential grid Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack grid ok
|
Electrical Rough-In | 5/23/2007 | 5/24/2007 | 5/24/2007 | A | PASS |
Bob Reichert
|
|
|
ug conduit; added ug j-box Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack correction made, ok to cover u/g, j-box will be in pavers west of pool towards pool equip
|
Electrical Rough-In | 5/21/2007 | 5/22/2007 | 5/22/2007 | A | FAIL |
Jack Frank
|
|
|
UG CONDUIT Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack corr 352.26 over 360 degree of bends home run do not cover called left message
|
Final | 5/15/2007 | 5/15/2007 | 5/15/2007 | P | PASS |
William E Thomas
|
|
|
pool bonding Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack bonding ok for the shell
|
Application received | | | 5/15/2007 | | DONE |
|
|
|
This permit was created on the web by Lee VanSchoiack
|
Change Status to I | | | 5/15/2007 | | DONE |
|
|
|
Final inspection should have been for a rough-in per BIll Thomas
|