Final | 5/16/2008 | 5/16/2008 | 5/16/2008 | P | PASS |
Bob Reichert
|
|
|
Thomas Phone #: ###-#### met owner, ok to final
|
Final | 5/9/2008 | 5/12/2008 | 5/12/2008 | P | CANC |
William E Thomas
|
|
|
Thomas Phone #: ###-####
|
Electrical Rough-In | 7/27/2007 | 7/30/2007 | 7/30/2007 | A | PASS |
Bob Reichert
|
|
|
tom Phone #: ###-#### master bath, bedroom and closet only ok to cover
|
Electrical Rough-In | 7/20/2007 | 7/20/2007 | 7/20/2007 | P | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/19/2007 at 5:13:30 PM. Contact: ###-####. see conf, too much too do for ri
|
Conference | 7/20/2007 | 7/20/2007 | 7/20/2007 | P | DONE |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/19/2007 at 5:13:30 PM. Contact: ###-####. met owner, explained stapling nm cable, make-up, not mixing 12 &14 off 20a bkr,
|
Electrical Rough-In | 7/19/2007 | 7/20/2007 | 7/20/2007 | A | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/19/2007 at 5:13:30 PM. Contact: ###-####. doing afternon inspection
|
Electrical Rough-In | 6/21/2007 | 6/22/2007 | 6/22/2007 | P | PART |
Bob Reichert
|
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang corr made, ric garage only ok
|
Electrical Rough-In | 6/14/2007 | 6/15/2007 | 6/15/2007 | P | FAIL |
Bob Reichert
|
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang met owner, BCC all make-up shall be done, nec 250.86 shall ground metal boxes, 210.70(A)(2) shall provide exit lite at mandoor in garage
|
Conference | 5/24/2007 | 5/25/2007 | 5/25/2007 | A | DONE |
Bob Reichert
|
|
|
tom ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith talked about bringing addition up to code
|
Application received | | | 5/23/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 5/23/2007 | | |
|
|
|
|