Final | 11/20/2007 | 11/21/2007 | 11/21/2007 | A | PASS |
Bob Reichert
|
|
|
Homeowner will be home Internet Inspection Request from: Todd Holbrook ok to final
|
Electrical Rough-In | 5/29/2007 | 5/29/2007 | 5/29/2007 | P | PASS |
Bob Reichert
|
|
|
rough in only ###-#### Internet Inspection Request from: Todd Holbrook called about recpt, nail plate, ric ok
|
Electrical Rough-In | 5/25/2007 | 5/25/2007 | 5/25/2007 | A | FAIL |
Bob Reichert
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook called, left message, left corr notice, nec 210.52(A)(2) there shall be recpt on 2' wall space(ne up br), 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 334.30 nm cable shall be stapled within 12" of panel, need to look at service when called in, check for sub-panel gnd and neut isol, range and dryer 4-wire
|
Application received | | | 5/25/2007 | | DONE |
|
|
|
This permit was created on the web by Todd Holbrook
|