Temporary Service | 5/30/2007 | 5/30/2007 | 5/30/2007 | P | PASS |
Bob Reichert
|
|
|
butch; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, t/s o/h n ok
|
Temporary Service | 5/25/2007 | 5/29/2007 | 5/29/2007 | A | FAIL |
Bob Reichert
|
|
|
schaffeld; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left corr notice, nec 250.53(G) ground rods shall be driven such that 8' is in contact with earth, and or 45 degrees or less, 590.6(B) ground fault protection shall be provided for other than 15 or 20a recpts, 312.5 abrasion protection shall be provided for all conductors entering enclosures, BCC job id sticker shall be posted
|
Reinspection Fee (no hold) | 5/29/2007 | 5/29/2007 | 5/29/2007 | A | FAIL |
Bob Reichert
|
|
|
schaffeld; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see failed inspection
|
Application received | | | 5/25/2007 | | |
|
|
|
|
Issue permit | | | 5/25/2007 | | DONE |
|
|
|
|