Second Notice ELE | 7/23/2007 | 7/23/2007 | 8/6/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 7/10/2007 | 7/10/2007 | 7/23/2007 | | DONE |
Jack Frank
|
|
|
|
Final | 7/9/2007 | 7/10/2007 | 7/10/2007 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 7/9/2007 at 10:04:17 PM. Contact: ###-####. ok card signed
|
Final | 7/8/2007 | 7/9/2007 | 7/9/2007 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 7/8/2007 at 7:57:03 PM. Contact: ###-####. corr 250.122 shall not use #12 for 30amp W H circuits from panel tp WH and all jboxes called
|
Permanent Service | 7/1/2007 | 7/2/2007 | 7/2/2007 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 7/1/2007 at 10:15:18 PM. Contact: ###-####. p/s u/g new ok
|
Permanent Service | 6/26/2007 | 6/27/2007 | 6/27/2007 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/26/2007 at 7:25:36 PM. Contact: ###-####. corr called all violations not done new one created shall use manufactures listed bonding means not a #10 jumper for 200 amp
|
Reinspection Fee (no hold) | 6/27/2007 | 6/27/2007 | 6/27/2007 | P | DONE |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/26/2007 at 7:25:36 PM. Contact: ###-####. all violations not made new one created
|
Final | 6/25/2007 | 6/26/2007 | 6/26/2007 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/25/2007 at 9:39:31 PM. Contact: ###-####. no pwer for new p/s can't do a final without power c alled
|
Reinspection Fee (no hold) | 6/26/2007 | 6/26/2007 | 6/26/2007 | P | DONE |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/25/2007 at 9:39:31 PM. Contact: ###-####. fee due, no power can't do final
|
Permanent Service | 6/25/2007 | 6/26/2007 | 6/26/2007 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/25/2007 at 9:38:46 PM. Contact: ###-####. called corr 250.92(A)(3) needs bonding both ends of conduit for GEC, shall terminate GEC to old GEC buse or tap to it, install bond strap at new 200 amp P/S needs labels noting both disconnects for tennant
|
Electrical Rough-In | 6/12/2007 | 6/13/2007 | 6/13/2007 | A | PASS |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 6/12/2007 at 2:00:41 PM. Contact: ###-####. walls ok to cover cielieng at later date
|
Electrical Rough-In | 6/11/2007 | 6/12/2007 | 6/12/2007 | P | FAIL |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 6/11/2007 at 7:53:29 PM. Contact: ###-####. 300.11 (b) & (c)
|
Electrical Rough-In | 6/8/2007 | 6/11/2007 | 6/11/2007 | A | FAIL |
Bob Reichert
|
|
|
Dave; Phone #: ###-#### Internet Inspection Request from: Hattie James called, left corr notice, nec 358.30(A) emt shall be supported within 12" of box, 330.30(B) mc cable shall be secured within 12" of box, and not over 6' in length without strapping,(whips) 300.4(A)&(D) edge of bored holes and raceways shall be 1 1/4" from edge of framing members, 300.11(A) support wires shall be provided for fixtures, BCC no violations shall be retained- no lv wiring on grid
|
Electrical Rough-In | 6/5/2007 | 6/6/2007 | 6/6/2007 | A | PART |
Jack Frank
|
|
|
Dave; pouring concrete - partial rough-in; Phone #: ###-#### Internet Inspection Request from: Hattie James u/g ok
|
Application received | | | 6/4/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/4/2007 | | DONE |
|
|
|
|