Final | 9/21/2007 | 9/21/2007 | 9/21/2007 | P | PASS |
Jack Frank
|
|
|
Dan, reinspection; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok
|
Final | 9/20/2007 | 9/20/2007 | 9/20/2007 | P | FAIL |
Jack Frank
|
|
|
dan Phone #: ###-#### 110.3(B) shall follow manufacture's instructions needs 16'x20' access and 20 amp configuration recept called corr. posted
|
Final | 9/19/2007 | 9/19/2007 | 9/19/2007 | A | FAIL |
Jack Frank
|
|
|
all correction not made and new one created still needs manufacture's info for jtub, panel schedule shall be secific purpose and use, new violation box fill island counter outlet called
|
Reinspection Fee (no hold) | 9/19/2007 | 9/19/2007 | 9/19/2007 | A | DONE |
Jack Frank
|
|
|
fee due more corrections and prior violations not corrected
|
Final | 9/18/2007 | 9/19/2007 | 9/19/2007 | A | NH |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/18/2007 at 9:56:38 PM. Contact: ###-####. called
|
Final | 9/17/2007 | 9/17/2007 | 9/17/2007 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/17/2007 at 7:23:30 AM. Contact: ###-####. fee due corr. called B,C,C, job note ready check all wiring, 314.16 box fill island outlet, 210.52(B) island disposal on S A B C , 210.52(D) outlet shall be within 3ft of all bath sinks, 210.52(C)(5) outlet too far under island overhang408.4 be specific panel schedule, 334.15 protect cables in island cabinet
|
Reinspection Fee (no hold) | 9/17/2007 | 9/17/2007 | 9/17/2007 | A | DONE |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/17/2007 at 7:23:30 AM. Contact: ###-####. fee due corr.
|
Rough-In Permanent Service | 7/12/2007 | 7/12/2007 | 7/12/2007 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 7/12/2007 at 7:35:52 AM. Contact: ###-####. survey posted called left message, 300.4(D) 11/4" for cables parallel, 334.23 protect cables 3ft of access
|
Rough-In Permanent Service | 7/10/2007 | 7/10/2007 | 7/10/2007 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 7/10/2007 at 7:30:32 AM. corr. not made see added p/s called
|
Permanent Service | 7/10/2007 | 7/10/2007 | 7/10/2007 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 7/10/2007 at 7:30:32 AM. p/s u/g new ok only
|
Reinspection Fee (no hold) | 7/10/2007 | 7/10/2007 | 7/10/2007 | A | DONE |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 7/10/2007 at 7:30:32 AM. fee due corr. not made
|
Electrical Rough-In | 6/19/2007 | 6/19/2007 | 6/19/2007 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/19/2007 at 6:55:17 AM. Contact: ###-####. corr. called l 300.4 nail plates and 11/4", 210.52(A&B) needs outlet kit west wall, 334.23 protect cables by attic accesses
|
Application received | | | 6/8/2007 | | |
|
|
|
|
Issue permit | | | 6/8/2007 | | DONE |
|
|
|
|