Second Notice ELE | 12/4/2007 | 12/4/2007 | 12/18/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 11/16/2007 | 11/16/2007 | 12/4/2007 | | DONE |
Pat Lass
|
|
|
|
Final | 11/15/2007 | 11/16/2007 | 11/16/2007 | A | PASS |
Pat Lass
|
|
|
skip Phone #: ###-#### no card
|
Final | 11/7/2007 | 11/8/2007 | 11/8/2007 | A | FAIL |
Bob Reichert
|
|
|
skip Phone #: ###-#### met contractor, left correction notice, nec 300.11(B) shall not suport low voltage wiring from raceways,314.25 in completed installations, boxes shall have covers installed, 400.8 shall not use cord above dropped ceiling
|
Final | 10/16/2007 | 10/17/2007 | 10/17/2007 | A | PART |
William E Thomas
|
|
|
bill Phone #: ###-#### . 1. T/O is approved. . . 2. we need to see grid in classroom. .
|
Final | 10/10/2007 | 10/11/2007 | 10/11/2007 | P | PART |
Pat Lass
|
|
|
skip Phone #: ###-#### 4 rooms not ready
|
Electrical Rough-In | 9/24/2007 | 9/25/2007 | 9/25/2007 | A | PART |
Bob Reichert
|
|
|
Skip; Phone #: ###-#### Internet Inspection Request from: Hattie James looked at furniture whips, listed and ok for hook-up, saw one piece furniture, listed ok, noted on plans
|
Electrical Rough-In | 9/19/2007 | 9/20/2007 | 9/20/2007 | A | PART |
Pat Lass
|
|
|
skip Note: coverup Phone #: ###-#### entry ceiling ok
|
Override - Parcel Holds | 9/19/2007 | 1/1/1900 | 9/19/2007 | | |
|
|
|
cover
|
Conference | 8/24/2007 | 8/27/2007 | 8/27/2007 | A | PART |
Pat Lass
|
|
|
skip Phone #: ###-#### talked about low voltage contractor
|
Electrical Rough-In | 7/27/2007 | 7/30/2007 | 7/30/2007 | A | PART |
Pat Lass
|
|
|
skip; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang walls anop
|
Permanent Service | 7/13/2007 | 7/13/2007 | 7/13/2007 | P | PART |
Pat Lass
|
|
|
skip Phone #: ###-####
r/I walls anop not for service
|
Electrical Rough-In | 7/5/2007 | 7/6/2007 | 7/6/2007 | P | PASS |
William E Thomas
|
|
|
skip; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie as noted on prints ok for cover
|
Electrical Rough-In | 6/29/2007 | 6/29/2007 | 6/29/2007 | P | PASS |
William E Thomas
|
|
|
skip Phone #: ###-#### as noted on prints ok
|
Electrical Rough-In | 6/19/2007 | 6/20/2007 | 6/20/2007 | A | PART |
Bob Reichert
|
|
|
skip ###-#### walls anop ok to cover, held back for fa, north 1/3 area 2nd floor
|
Application received | | | 6/8/2007 | | |
|
|
|
|
Issue permit | | | 6/8/2007 | | DONE |
|
|
|
|