Final | 6/14/2007 | 6/15/2007 | 6/15/2007 | A | PASS |
Bob Reichert
|
|
|
Inspection for correction of motor disconnect. Thank you Bob!! Phone #: ###-#### Internet Inspection Request from: Lynn Solmon corr made, ok to final
|
Final | 6/13/2007 | 6/14/2007 | 6/14/2007 | A | CANC |
Bob Reichert
|
|
|
Inspect new shed service for irrigation pump & control; trench also for future shop. Phone #: ###-#### Internet Inspection Request from: Lynn Solmon wrong type request, see rip
|
Rough-In Permanent Service | 6/14/2007 | 6/14/2007 | 6/14/2007 | A | FAIL |
Bob Reichert
|
|
|
Inspect new shed service for irrigation pump & control; trench also for future shop. Phone #: ###-#### Internet Inspection Request from: Lynn Solmon called left corr notice, nec 352. 26 there shall not be over 360 degree total bend in raceway, 430.102(B) motor disconnect shall be insight of motor, ok to cover u/g up to motor location and towards new shop by shed, told to recall
|
Application received | | | 6/13/2007 | | DONE |
|
|
|