Final | 9/24/2007 | 9/24/2007 | 9/24/2007 | P | PASS |
Bob Reichert
|
|
|
dave - please call for acess Phone #: ###-#### corrections made, ok to final
|
Final | 9/20/2007 | 9/21/2007 | 9/21/2007 | A | FAIL |
Jack Frank
|
|
|
DAVE Phone #: ###-#### corr. fee due called 210.52(A) needs outlet liv. rm by fireplace and eating bar wall space, 410.8 clearence for all bed rm closet fixtures, box fill old metal box basement W H drain pump called left message
|
Reinspection Fee (no hold) | 9/21/2007 | 9/21/2007 | 9/21/2007 | A | DONE |
Jack Frank
|
|
|
DAVE Phone #: ###-#### fee due corrections
|
Electrical Rough-In | 7/19/2007 | 7/19/2007 | 7/19/2007 | P | PASS |
William E Thomas
|
|
|
randy Phone #: ###-#### 1. upstairs ok--the first floor
|
Electrical Rough-In | 7/17/2007 | 7/17/2007 | 7/18/2007 | P | FAIL |
Bob Reichert
|
|
|
randy Phone #: ###-#### called, left message, left corr notice, nec 210.52 shall provide recpts at front and rear of dwelling, in hall over 10' long, in walls over 2', within 6' of room entry and not over 12' apart along wall line, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.17 shall staple nm cable within 8" or 12" of appropriate boxes, 300.14 shall provide 6" free conductor length at boxes, BCC no violations shall be retained
|
Permanent Service | 6/25/2007 | 6/25/2007 | 6/25/2007 | P | PASS |
Bob Reichert
|
|
|
randy Phone #: ###-#### corrections made, p/s o/h rec ok
|
Permanent Service | 6/20/2007 | 6/20/2007 | 6/20/2007 | P | FAIL |
Bob Reichert
|
|
|
joe Phone #: ###-#### called , corrections not done plus created new violations, nec 312.5 shall provide abrasion protection for all conductors entering enclosures, 250.64(C) shall use irreversible splice on gec, did not fix panel door or ground water pipe,fee due
|
Reinspection Fee (no hold) | 6/20/2007 | 6/20/2007 | 6/20/2007 | P | FAIL |
Bob Reichert
|
|
|
joe Phone #: ###-#### corr not made
|
Permanent Service | 6/15/2007 | 6/15/2007 | 6/15/2007 | P | FAIL |
Bob Reichert
|
|
|
randy ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice, nec 352.30 & 358.30 conduit shall be supported within 3' of panel, 110.12(C) there shall be no damaged parts-panel cover hinge, grounding electrode conductor, 250.52(A) shall use metal water pipe for gnd electrode,210.53(D)(2) shall supplement electrode with 2 ground rods, 210.53(G) grd rods shall be driven 8' into ground, upper end flush with or below ground, 110.3(B) shall use listed gnd clamps,BCC no violations shall be retained
|
Application received | | | 6/15/2007 | | |
|
|
|
|
Issue permit | | | 6/15/2007 | | DONE |
|
|
|
|