Final | 6/20/2007 | 6/21/2007 | 6/21/2007 | A | PASS |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 6/20/2007 at 7:57:58 PM. Contact: ###-####. final ok-- ri p/s o/h reconnect ok
|
Final | 6/19/2007 | 6/19/2007 | 6/19/2007 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/19/2007 at 7:29:32 AM. called left corr notice, nec 110.3(B) listed equipment shall be installed per instructions, 110.14(A) connections shall be tight, 110.12(C) paint shall not contaminate wiring, 250.52(A) shall use metal water pipe for grounding electrode, 250.64(C) grounding electrode conductor shall be installed in one continuous length without a splice or joint
|
Application received | | | 6/18/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/18/2007 | | DONE |
|
|
|
|