(F) Reprint permit | | | 6/25/2007 | | DONE |
|
|
|
|
Temporary Service | 6/20/2007 | 6/20/2007 | 6/20/2007 | P | PASS |
Bob Reichert
|
|
|
greg; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang corr made, t/s o/h n ok
|
Temporary Service | 6/19/2007 | 6/19/2007 | 6/19/2007 | P | FAIL |
Jack Frank
|
|
|
greg ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith fee due corr. called 312.5 needs conn for GEC, 110.12(C) clean dirt from t/s and receptacles, 250.52(A)(5)7250.23(G) short grd rod
|
Reinspection Fee (no hold) | 6/19/2007 | 6/19/2007 | 6/19/2007 | P | DONE |
Jack Frank
|
|
|
greg ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith fee due corr. posted
|
Application received | | | 6/18/2007 | | |
|
|
|
|
Issue permit | | | 6/18/2007 | | DONE |
|
|
|
|