Final | 10/11/2007 | 10/11/2007 | 10/11/2007 | A | PASS |
Bob Reichert
|
|
|
met contractor, ok to final, people moved in, looked at receptacles that could get to only
|
Final | 10/9/2007 | 10/11/2007 | 10/10/2007 | A | CANC |
Bob Reichert
|
|
|
jack - please call 1/2 hr prior to inspection Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|
Permanent Service | 9/10/2007 | 9/11/2007 | 9/11/2007 | A | CANC |
Bob Reichert
|
|
|
jack Phone #: ###-#### wrong permit and address,see added inspection for next door ( ele07-02775)
|
Electrical Rough-In | 6/29/2007 | 6/29/2007 | 6/29/2007 | P | PASS |
Bob Reichert
|
|
|
JACK Phone #: ###-#### corrections made, ric ok
|
Electrical Rough-In | 6/25/2007 | 6/25/2007 | 6/25/2007 | P | FAIL |
Bob Reichert
|
|
|
jack Phone #: ###-#### called, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) outlets shall be spaced such that no point along wall line is over 6' from an outlet,210.52(H)hallways over 10' shall have an outlet, 210.52(E) there shall be an outlet at front and rear of dwelling, 110.26(F)(1)(b) there shall be no ducts in dedicated space over panel BCC no violations shall be retained,nm cable shall run thru holes in studs, framing shall be done for inspection
|
Application received | | | 6/21/2007 | | |
|
|
|
|
Issue permit | | | 6/21/2007 | | DONE |
|
|
|
|