Case Summary (ELE) | | | 5/14/2008 | | DONE |
|
|
|
|
Case Summary (ELE) | | | 5/14/2008 | | DONE |
|
|
|
|
Third Notice ELE | 10/12/2007 | 10/12/2007 | 10/17/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Third Notice ELE | 10/12/2007 | 10/12/2007 | 10/17/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 9/26/2007 | 9/26/2007 | 10/12/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
Second Notice ELE | 9/26/2007 | 9/26/2007 | 10/12/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
Telephone call | | | 10/8/2007 | | DONE |
|
|
|
tlk to dan ###-#### about the final fees which are their company fees not 40,304 12:00 pm
|
First Notice | 9/7/2007 | 9/7/2007 | 9/26/2007 | | DONE |
Bob Reichert
|
|
|
|
First Notice | 9/7/2007 | 9/7/2007 | 9/26/2007 | | DONE |
Bob Reichert
|
|
|
|
Final | 9/6/2007 | 9/7/2007 | 9/7/2007 | P | PASS |
Bob Reichert
|
|
|
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final, signed occ card
|
Electrical Rough-In | 9/7/2007 | 9/7/2007 | 9/7/2007 | P | PASS |
Bob Reichert
|
|
|
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to cover ceiling
|
Permanent Service | 8/27/2007 | 8/27/2007 | 8/27/2007 | P | PASS |
William E Thomas
|
|
|
dan Phone #: ###-#### 1. P/S N OK-- A METER IS ALL THAT IS NEEDED FOR THIS INSTALL.
|
Electrical Rough-In | 7/20/2007 | 7/20/2007 | 7/20/2007 | P | PASS |
Bob Reichert
|
|
|
dan - wall cover; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang corrections made, ric walls and hard lids only ok to cover
|
Electrical Rough-In | 7/19/2007 | 7/19/2007 | 7/19/2007 | P | FAIL |
Bob Reichert
|
|
|
dan - ok to cover on the walls only Phone #: ###-#### called left corr notice, nec 330.30 (B) mc cable shall be strapped within 12" of box, 110.12(A) unused openings shall be closed, 100.3(B) shall use approved equipment and per mfgr's instructions, BCC all make-up shall be done, no wiring in valley of framing members shall be done, address shall be posted
|
Electrical Rough-In | 6/21/2007 | 6/22/2007 | 6/22/2007 | A | PASS |
Bob Reichert
|
|
|
dan Phone #: ###-#### u/g for 2" cnd only ok to pour
|
Electrical Rough-In | 6/21/2007 | 6/21/2007 | 6/21/2007 | P | CANC |
William E Thomas
|
|
|
ian; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang no access, doors locked
|
Application received | | | 6/21/2007 | | |
|
|
|
|
Issue permit | | | 6/21/2007 | | DONE |
|
|
|
|