DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary (ELE)  5/14/2008 DONE
Case Summary (ELE)  5/14/2008 DONE
Third Notice ELE10/12/200710/12/200710/17/2007 DONE
Second Notice has not been responded to.
Third Notice ELE10/12/200710/12/200710/17/2007 DONE
Second Notice has not been responded to.
Second Notice ELE9/26/20079/26/200710/12/2007 DONE
First Notice has not been responded to.
Second Notice ELE9/26/20079/26/200710/12/2007 DONE
First Notice has not been responded to.
Telephone call  10/8/2007 DONE
tlk to dan ###-#### about the final fees which are their company fees not 40,304 12:00 pm
First Notice9/7/20079/7/20079/26/2007 DONE
DetailsBob Reichert
First Notice9/7/20079/7/20079/26/2007 DONE
DetailsBob Reichert
Final9/6/20079/7/20079/7/2007PPASS
DetailsBob Reichert
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final, signed occ card
Electrical Rough-In9/7/20079/7/20079/7/2007PPASS
DetailsBob Reichert
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to cover ceiling
Permanent Service8/27/20078/27/20078/27/2007PPASS
DetailsWilliam E Thomas
dan Phone #: ###-####
1. P/S N OK-- A METER IS ALL THAT IS NEEDED FOR THIS INSTALL.
Electrical Rough-In7/20/20077/20/20077/20/2007PPASS
DetailsBob Reichert
dan - wall cover; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang corrections made, ric walls and hard lids only ok to cover
Electrical Rough-In7/19/20077/19/20077/19/2007PFAIL
DetailsBob Reichert
dan - ok to cover on the walls only Phone #: ###-#### called left corr notice, nec 330.30 (B) mc cable shall be strapped within 12" of box, 110.12(A) unused openings shall be closed, 100.3(B) shall use approved equipment and per mfgr's instructions, BCC all make-up shall be done, no wiring in valley of framing members shall be done, address shall be posted
Electrical Rough-In6/21/20076/22/20076/22/2007APASS
DetailsBob Reichert
dan Phone #: ###-#### u/g for 2" cnd only ok to pour
Electrical Rough-In6/21/20076/21/20076/21/2007PCANC
DetailsWilliam E Thomas
ian; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
no access, doors locked
Application received  6/21/2007  
Issue permit  6/21/2007 DONE