Final | 9/25/2007 | 9/26/2007 | 9/26/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla ok to final fouse, elect will permit hot tub separately
|
Rough-In Permanent Service | 6/30/2007 | 7/2/2007 | 7/2/2007 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla corrections made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 6/28/2007 | 6/28/2007 | 6/28/2007 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called, left corr notice, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members (in and outside edges), 334.30 nm cable shall be stapled within 12" of panel, 110.12(C) there shall be no broken parts (outside lite box towards rear), 210.52(A)(2) there shall be recpts installed in 2' wall space and 6' at entry to room (kitchen and family room) BCC address shall be corrected on all permits, yellow card states north, not south
|
Application received | | | 6/28/2007 | | DONE |
|
|
|
This permit was created on the web by Cevyn Recla
|