Final | 10/10/2007 | 10/11/2007 | 10/11/2007 | A | PASS |
Jack Frank
|
|
|
eric - re-inspection Phone #: ###-#### ok
|
Final | 10/9/2007 | 10/10/2007 | 10/10/2007 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/9/2007 at 12:02:52 PM. Contact: ###-####. corr. 408.4 panel directory be specific, 410,8 clearence for closet fixtures, and install all closet fixtures, called
|
Reinspection Fee (no hold) | 10/10/2007 | 10/10/2007 | 10/10/2007 | A | DONE |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/9/2007 at 12:02:52 PM. Contact: ###-####. fee due corr.
|
Rough-In Permanent Service | 7/5/2007 | 7/6/2007 | 7/6/2007 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 7/5/2007 at 11:39:37 AM. Contact: ###-####. r/i ok corr. made found listing on tub
|
Rough-In Permanent Service | 7/2/2007 | 7/3/2007 | 7/3/2007 | A | FAIL |
Jack Frank
|
|
|
zane Phone #: ###-#### see added p/s , r/i failed install for boxes, complete all makeup outsie boxes, 334.23 protect all cables high and low volt by attic accesses, 300.4(A)(1)&(D) nail plates and 11/4" for low voltage, 110.2 Jtub not listed by testing lab called
|
Permanent Service | 7/3/2007 | 7/3/2007 | 7/3/2007 | A | PASS |
Jack Frank
|
|
|
zane Phone #: ###-#### p/s u/g new ok
|
Electrical Rough-In | 6/28/2007 | 7/2/2007 | 7/2/2007 | A | FAIL |
Bob Reichert
|
|
|
jason Phone #: ###-#### called, left message, 219.52(A)(1) recpts shall be installed such that no point along wall is over 6' from outlet, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member
|
Application received | | | 6/28/2007 | | |
|
|
|
|
Issue permit | | | 6/28/2007 | | |
|
|
|
|