Final | 8/15/2007 | 8/15/2007 | 8/15/2007 | P | PASS |
Bob Reichert
|
|
|
Carol; Phone #: ###-#### Internet Inspection Request from: Hattie James corrections made, ok to final
|
Final | 8/14/2007 | 8/14/2007 | 8/14/2007 | P | FAIL |
Bob Reichert
|
|
|
Cell: ###-####; Carol; Phone #: ###-#### Internet Inspection Request from: Hattie James called, left corr notice, nec 406.8(B) recpts in wet location shall have enclosure that is weatherproof whether or not plug inserted, 210.8(A)(2) gfci shall be provided for all recpts in garage or accessory bldg
|
Electrical Rough-In | 8/6/2007 | 8/6/2007 | 8/6/2007 | P | PASS |
Bob Reichert
|
|
|
carol - re-inspection Phone #: ###-#### corrections made, ric ok
|
Electrical Rough-In | 8/2/2007 | 8/2/2007 | 8/2/2007 | P | FAIL |
Bob Reichert
|
|
|
carol Phone #: ###-#### met owner, left corr notice, nec 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing members, 110.26(A) shall provide work space in front of sub-panel in garage
|
Conference | 7/2/2007 | 7/3/2007 | 7/3/2007 | P | DONE |
Bob Reichert
|
|
|
James ###-#### talked about inside wiring for new storage building or shop, owner said service will be by others, said to watch for 1 1/4" make-up free conductor length, told owner if only 1 recpt on 20a ckt, then shall have 20a recpt, but if more than one recpt, can be 15a
|
Issue PAID IN FULL permit | | | 7/2/2007 | | DONE |
|
|
|
|
Application received | | | 7/2/2007 | | |
|
|
|
|