Permit Information
Permit NumberELE07-02487
StatusFinaled
Name ACE ELECTRIC AND CONTROL
Site Address 2018 S GOLDKING WAY
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration: Add recessed lighting to kitchen, modify switching, add recessed lighting to dining and entry(cut in)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/17/20079/17/20079/17/2007APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Monty Adkinson called contr about dishwasher lock-out, ok to final
Electrical Rough-In7/17/20077/17/20077/17/2007APASS
DetailsBob Reichert
kitchen, dining, entry work, corrections made. Phone #: ###-#### Internet Inspection Request from: Monty Adkinson corrections made, ric ok
Electrical Rough-In7/16/20077/16/20077/16/2007AFAIL
DetailsBob Reichert
need cover inspection in exposed areas, added recessed cans are cut in through existing sheetrock in dining and entry areas Phone #: ###-#### Internet Inspection Request from: Monty Adkinson called, left message, left corr notice, nec 110.12(C) there shall be no broken parts or equipment, i.e. box shall not have clamps broken out, nm cable shall not have damaged jacketing, 300.4(D) nm cable shall be 1 1/4" from edge of framing member
Application received  7/16/2007 DONE
This permit was created on the web by Monty Adkinson