Telephone call | | | 2/13/2008 | | DONE |
|
|
|
lft vm with boise elect to verify the final value from cert of value 2:10
|
Second Notice ELE | 8/8/2007 | 8/8/2007 | 8/10/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 7/19/2007 | 7/19/2007 | 8/8/2007 | | DONE |
Pat Lass
|
|
|
|
Final | 7/19/2007 | 7/19/2007 | 7/19/2007 | P | PASS |
Pat Lass
|
|
|
glen Phone #: ###-####
|
Final | 7/18/2007 | 7/18/2007 | 7/18/2007 | P | PART |
Pat Lass
|
|
|
GLEN Phone #: ###-#### glen's part is ok low voltage not secured loose set screws
|
Final | 7/17/2007 | 7/18/2007 | 7/18/2007 | A | NR |
Pat Lass
|
|
|
glen; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
|
Electrical Rough-In | 7/17/2007 | 7/18/2007 | 7/18/2007 | A | FAIL |
Pat Lass
|
|
|
glen; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang 358.30 Securing and Supporting. EMT shall be securely fastened in place and supported 358.42 Couplings and Connectors. Couplings and connectors used with EMT shall be made up tight. 110.12 Mechanical Execution of Work. (A) Unused Openings. 300.11 Securing and Supporting. (B) Raceways Used as Means of Support.
|
Application received | | | 7/17/2007 | | |
|
|
|
|
Issue permit | | | 7/17/2007 | | DONE |
|
|
|
|