Final | 10/8/2007 | 10/8/2007 | 10/8/2007 | P | PASS |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 10/8/2007 at 8:18:03 AM. Contact: ###-####. . 1. final ok. .
|
Final | 10/4/2007 | 10/4/2007 | 10/4/2007 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/4/2007 at 9:17:46 AM. Contact: ###-####. corr. called 210.52(A) needs recept east wall fam. rm. right of builtin cabinet, within 6ft outlet for TV set too hign to serve wall space it's over 51/2 ft, 408.4 panel schedule be specific purpose and use all breakers, 210.8 all new outlets in garage need gfci
|
Reinspection Fee (no hold) | 10/4/2007 | 10/4/2007 | 10/4/2007 | P | DONE |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/4/2007 at 9:17:46 AM. Contact: ###-####. fee due corr.
|
Reinspection Fee (no hold) | 9/28/2007 | 9/28/2007 | 9/28/2007 | P | NH |
Bob Reichert
|
|
|
see nh response
|
Final | 9/28/2007 | 9/28/2007 | 9/28/2007 | P | NH |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/28/2007 at 9:23:11 AM. Contact: ###-####. called, said to call when somebody there
|
Electrical Rough-In | 7/19/2007 | 7/20/2007 | 7/20/2007 | A | PASS |
Mike Kinnear
|
|
|
john Phone #: ###-#### ok cover ri
|
Application received | | | 7/19/2007 | | |
|
|
|
|
Issue permit | | | 7/19/2007 | | |
|
|
|
|