Final | 11/27/2007 | 11/28/2007 | 11/28/2007 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: JAMES GARCES ok
|
Final | 11/5/2007 | 11/6/2007 | 11/6/2007 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: JAMES GARCES called needs gfci recept 10 ft 20 ft for spa
|
Electrical Rough-In | 10/12/2007 | 10/12/2007 | 10/12/2007 | P | PASS |
Bob Reichert
|
|
|
Equipotential Bonding Grid Wet -niche potting Phone #: ###-#### Internet Inspection Request from: JAMES GARCES e-plane ok to cover, potting ok
|
Electrical Rough-In | 10/8/2007 | 10/9/2007 | 10/9/2007 | P | FAIL |
Jack Frank
|
|
|
Grounding electrode conductor---ground rods and Equipotential Boding Grid Phone #: ###-#### Internet Inspection Request from: JAMES GARCES called told ele contr what "s required when pavers are used instead of concrete for E grid
|
Electrical Rough-In | 9/24/2007 | 9/24/2007 | 9/24/2007 | A | FAIL |
Jack Frank
|
|
|
CHECK GROUND RODS---MAIN BREAKER Phone #: ###-#### Internet Inspection Request from: JAMES GARCES called left message protect #8 GEC, needs conn for GEC, bonding pool equip tie #8 together
|
Electrical Rough-In | 9/18/2007 | 9/19/2007 | 9/19/2007 | A | PART |
Jack Frank
|
|
|
Inspection is for bonding of spa. and electrical work and bonding in pump house Phone #: ###-#### Internet Inspection Request from: JAMES GARCES spa bond ok no E grid and rump house failed called left message needs grd rods, main breaker and using #8 pool bond as GEC COW
|
Electrical Rough-In | 7/24/2007 | 7/25/2007 | 7/25/2007 | A | PASS |
William E Thomas
|
|
|
james; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang 1. bond wire to equipment ok 2. underground ok
|
Application received | | | 7/24/2007 | | |
|
|
|
|
Issue permit | | | 7/24/2007 | | DONE |
|
|
|
|