Final | 10/2/2007 | 10/2/2007 | 10/2/2007 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr, ok to final
|
Permanent Service | 8/20/2007 | 8/20/2007 | 8/20/2007 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters Inspection cancelled from web by: Celinda Winters
|
Rough-In Permanent Service | 8/10/2007 | 8/10/2007 | 8/10/2007 | P | PASS |
Bob Reichert
|
|
|
corrections made Phone #: ###-#### Internet Inspection Request from: Celinda Winters coorr made, ric ok p/s o/h rec ok
|
Rough-In Permanent Service | 8/9/2007 | 8/9/2007 | 8/9/2007 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called, left corr notice, nec 110.3(B) shall install gec clamp per mfgr's instructions included with listing, 250.52(A)(1) shall use metal water pipe for grounding electrode, 250.64(B) shall protect or staple gec to bldg, 250.53(G) electrodes shall be flush with or below ground, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members or use steel plate, 334.30 shall strap nm cable within 12" of panel, 410.8 shall provide clearances for closet lights,BCC all make-up shall be done, guy kit shall be installed
|
Application received | | | 7/24/2007 | | DONE |
|
|
|
This permit was created on the web by Celinda Winters
|