Final | 12/27/2007 | 12/27/2007 | 12/27/2007 | A | PASS |
Jack Frank
|
|
|
alraedy inspected by 370 final ok
|
Rough-In Permanent Service | 8/3/2007 | 8/3/2007 | 8/3/2007 | P | PASS |
Bob Reichert
|
|
|
permanent service and trench Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ric ok, u/g ok to cover, p/s u/g n ok
|
Permanent Service | 8/2/2007 | 8/2/2007 | 8/2/2007 | P | FAIL |
Bob Reichert
|
|
|
permanent service and underground Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called left corr notice, nec 300.5 raceways shall be 18" deep to top conduit, 250.28 shall install main bonding jumper screw in shop panel, 408.4 shall provide circuit directory, 110.26(A) shall provide workspace in front of sub-panel in garage to check for isolated ground and neutral
|
Application received | | | 7/26/2007 | | DONE |
|
|
|
This permit was created on the web by Jarrod Clymer
|