Third Notice ELE | 9/7/2007 | 9/7/2007 | 9/14/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 8/22/2007 | 8/22/2007 | 9/7/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 8/3/2007 | 8/3/2007 | 8/22/2007 | | DONE |
Jack Frank
|
|
|
|
Permanent Service | 8/3/2007 | 8/3/2007 | 8/3/2007 | P | PASS |
Jack Frank
|
|
|
gene - re-inspection Phone #: ###-#### p/s u/g new ok
|
Final | 8/3/2007 | 8/3/2007 | 8/3/2007 | P | PASS |
Jack Frank
|
|
|
gene - re-inspection Phone #: ###-####
|
Permanent Service | 8/2/2007 | 8/3/2007 | 8/3/2007 | A | FAIL |
Jack Frank
|
|
|
gene Phone #: ###-#### corr called left message 250.92(A)(3) bond both end of emt for GEC, 110.14 wirenut not listed for cual, 110.3(B) switch shall use manufactures listed grd bar kit for suzi rating, 250.24 shall terminate GEC to grounded conductor at service, shall not use telephone L fitting for electrical wiring
|
Reinspection Fee (no hold) | 8/3/2007 | 8/3/2007 | 8/3/2007 | A | DONE |
Jack Frank
|
|
|
gene Phone #: ###-#### fee due corr. not made more created
|
Permanent Service | 8/2/2007 | 8/2/2007 | 8/2/2007 | A | FAIL |
Jack Frank
|
|
|
JEAN Phone #: ###-#### called left message corr. needs manufactures listed kit for suzi rating for disconnect, protect #8 GEC or use #6, conn for GEC
|
Permanent Service | 7/31/2007 | 8/1/2007 | 8/1/2007 | A | CANC |
Jack Frank
|
|
|
JEAN Phone #: ###-####
|
Application received | | | 7/31/2007 | | |
|
|
|
|
Issue permit | | | 7/31/2007 | | DONE |
|
|
|
|